Loading...
HomeMy WebLinkAboutOrdinances_2105 CORRECTED 9/23/90 AMENDED BY ORD- 2188 ORDINANCE NO. 210S AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF REDLANDS AAENDIANG CHAPTER 15 . 20 OF THE REDLANDS MUNICIPAL CODE BY ADOP'^- ING THE UNIFORM FIRE CODE, 1988 EDITION WHEREAS, Government Code Section 50020 et sect, empowers the City to adopt by reference various uniform codes , inclining the Uniform Fire Code; and WHEREAS , the City Council is informed and finds that the Uniform Fire Code , 1988 Edition, rust be amended to meet the particular climatic, geological and topographical condi- tions existing in the City; and WHEREAS, the City Council is informed and finds that these climatic , geological, and topographical conditions include, but are not limited to the Eollgwing conditions : 1 , The City is subject to relatively low amounts of precipitation, very low humidity levels and extremely high temperatures . These climatic conditions are condusive to the spread of fare . For example , during July, August and September , temperatures often exceed 100° Fahrenheit . During the same months humidity is usually less than 40%, and measurements less than 101 are not uncommon . These recordings were documented by the San Bernardino County Flood Control District and the National Climatic Data Center . 2 . The City is subject to extremely strong rinds , commonly referred to as "Santa Ana winds , " which Can reach speeds Of 80 miles ger hour . Extensive damage often occurs during such winds including downed trees , utility poles, utility circuits and utility service lines . These adverse conditions cause : ( 1 ) fires, ( 2 ) impairment of emergency apparatus access , ( 3 ) delays in response times of emergency apparatuS , and ( 4 ) the depletion of apparatus readily available for Fire suppression activities . For example , one wind storm lasted for approximately six hours and downed, over 200 trees Citywide in 1985 . In 1989 , the City experienced a 24 hour period of severe winds during which scares of utility lines were downed in the Citi► impairing emergency access . On one occasion fire units from Redlands were sent to assist in the extinguishment of a fast moving, wind assisted Fire in the Sari Bernardino Eighland Foothills which destroyed or damaged many homes . These units were then unavailable for fire suppression in the City . 3 . Within tri@ City there are four earthquake faults ( Redlands Heights Fault , Banning Fault , Crafton Fault and the Redlands Fault ) : three other faults are located in immediately adjacent areas ( Loma Linda -2- Fault, San Jacinto Fault and the San Andz eas Fault ) . In the event of a severe earthquake , these faults present the potential Eor catastrophic damage , includ- ing fire , damage to roadways and other impairments of emergency apparatus , ( This information is according to maps used by Cal Tech , Pasadena and provided by the U . S . Geological Survey. ) WHEREAS , the City Council is informed and finds that development has occurred in the City and continues to occur that has resulted in severe traffic conjestion during peak business hours, weekends and holidays thus , decreasing response time particularly on the following streets and highways : Citrus Avenue, Cajon Street , Grange Street , I,ugonia Avenue , Colton Avenue , Tennessee Street , San Timeteo Canyon Road, and I-10 Freeway; and WHEREAS , the City Council is i�xvrter] and finds that automatic fire protection systema are the single greatest means of reducing the severity of structural fires and that fire loss in unsprinklered buildings is four times greater than fire loss in spri.nklered buildings : and WHEREAS, the City Council is informed and finds that no single fire causing three or more fatalities has occurred in sprinklered residential structures ;including houses , apart- ment-s , mobile +comes , hotels , motels and dormitories and that these Fatalities were the result of explosions or other -3- occurrences rendering fystems inoperable or as the result of Clothing being ignited on the person . NOW, THEREFORE, the City COuncil of the Citi+ of Redlands does ordain as follows : SECTION 1 : Chapter 15 . 20 of Title 15 OF the Redlands Municipal Cade is hereby amended to read as follows : ItChapter 15. 20 UNIFORM FIRE CODE SECTIONS: 15.20. 010 Uniform Fire Code adopted by reference -- Dopy on file. 15 . 20 . 011 Definitions . 15 . 24 . 012 Modifications. 15 . 20 . 015 QFC Article 2 amended organization and authority. 15 . 20 . 020 UFC Section 9 . 103 amended -- additional definition&. 15 . 24 . 025 QFC Article 10 amended -- fire protection. 15 . 20 . 030 UFC Article 11 amended -- general precautions against fiCe . 15 . 20 . 032 UFC Article 14 amended -- fire alarm systems . 15 . 20 . 035 UFC Article 25 amended -- places of assembly . 15 . 20 , 040 UFC Section 61 _ 106(c ) amended -- portable unvented oil - burning heating appliances. 15 . 20 . 042 UFC Article 77 amended -- explosives and blasting agents, 15 . 20 . 045 UFC Article 79 amended -- flammable and combustible liquids. 15 . 20 . 055 QFC Section 62, 104 amended _ - location of containers . 15. 20.060 UFC Section 85. 104 amended abatement of electrical ha, tards . 15, 20 .065 UPC Appendix I-A amended -- life safety requirements for existing buildings other that high rise. 15 . 20. 067 UPC Appendix I-B amended -- life safety requirements for existing high rise buildings . 15 . 20 . 070 UFC Appendix 11-A amended -- suppression and control of hazardous fire areas. -5- 15. 20. 075 Limits of districts in which storage of combustible liquids is prohibited. 15 . 20 .076 Limits of districts in which bulk storage of liquified petroleum gas is restricted. 15. 20.077 Limits of districts in which starage of expIcsives and blasting agents is prohibited. 15. 20.880 Permit requirements and appeals . 15 . 20 . 090 New materials, processes or occu- pancies which may require permits. 15. 20. 100 Enforcement -- fire chie-f authority. 15 . 20.110 Citation issuance authority. 15. 20. 120 Violation y-- penalty . 15 . 20 . 010 Uniform Fire Code adopted by reference -- copy on file . That certain document on file in the office of the city Clerk, which is marked and designated as Uniform Fire Code , 1988 Edition , including Appendices I-A, I-9, II-A, 11-9, II--D, II-E, III-A, III-B, III-C, IV-A, V-A, VI-CP providing regulations consistent with nationally recognized standard practices to safeguard life , health , property and the public welfare from the hazards of Eire and explosion , -6- are adopted by reference and made a part of this code . One copy of the code and the appendices has been certified as a true copy and filed in the office of the City Clerk . The code and appendices so adopted by reference and made a part of this chapter as though set forth at length in this chapter . Except where otherwise indicated, all references in this chapter to the Uniform Fire Code shall include the appendices to the Uniform Fire Code and the amendments to such Code and such appendices contained in this Code. 15 . 20 . 011 Definitions . (a ) Wherever the word "Municipality" is used in said Uniform Fire Cade , it shall mean the City of Redlands . (b ) wherever the term "Corporation Counsel" is used in said Uniform Fire Code , it shall mean the City Attorney for the City of Redlands . { c} Wherever the term "Fire Prevention Engineer , " "F ire Marshal , " "Fire Prevention officer, " or "Chief of the Bureau of Fire Prevention" is used in said Uniform Fire Code , it shall mean that Chi-ef Officer designated by the Fire Chief as being in chane of the Fire Prevention Bureau . 15 . 20 . 012 Modifications . (a) The provisions of this Code shall apply to existing conditions as well as to conditions arising after the adoption thereof , except that conditions legally in -7- existence at the adoption of this Code and not in strict compliance therewith shall be permitted to continue only if , in the opinion of the Chief of the Fire Prevention Bureau and the concurrence of the City Manager , they do not consti- tute a distinct hazard of life and property . ( b ) The Chief of tete Fire Prevention Bureau small have the power to modify any of the prcvisions of said Uniform Fire Code Lipon an application in writing by the owner or lessee, or his duly authorized agent , when there are practical difficulties in the way of carrying out the strict letter of the code ; provided, however , the spirit of the code shall be observed , public safety secured, and sub- stantial justice done. The particulars of such modifica- tion , when granted or allowed, and the decision of the Chief of the Eire Prevention Bureau thereof shall be entered upon the records of the department , and a signed ropy shall be furnished the applicant . 1.5 . 20 . 015 UFC Article 2 amended -- organization and authority . Article 2 of the Uniform Fire Code is amended by rewriting Section 2 . 108 and by adding Section 2 . 304 ( b) as follows : Section 2 . 108 . Liability for damages . - . (a ) This code shall not be con- strued so as to hold the City of Redlands or any officer or employee of -8- the City responsible for any damage to persons or property by reason of inspec- tion , reinspection or any failure to inspect as provided herein , or by reason of the approval or disapproval of any equipment or process authorized herein or for any action or omission in connec- tion with the control ar extinguishment of any fire or in connection with any other official duties . ( b ) Fire suppression , investiga- tion and rescue , and emergency medical costs shall be recoverable by the City in accordance with the provisions of California Health and Safety Code Sections 13009 and 13049 . 1 . ( c) Any person who negligently , intentionally or in violation of law, causes an emergency response, including, but not limited to a traffic accident or spill of toxic or flammable fluids or chemicals , shall be liable for the costs of responding to such emergency, includ- ing those costs set forth in Health and Safety Cade Section 13449 . 6, and as pro- vided by Government Code Section 53154 , et seq. Any expense incurred by the FYre Department in responding to such an emergency shall constitute a debt of such person and shall be collectible by the City in the safne manner as in the case of an obligation under contract , express or implied . Section 2 . 304 . Current editions . ( b) More current editions of these publications or supplements thereto may apply if the intent of the listed stan- dards remain unchanged . 15. 20 . 020 UFC Section 9 . 103 amended -- additional defini- tions . Section 9 . 103 of the Uniform Fire Cade is amended by adding the fallowing definition: -9- Section 9 . 103 . AIL-WEATHER DRIVING SURFACE is a concrete or asphalt cover- ing over base material and a roadbed compacted t0 95% and of sufficient thicknesra to suppart the imponed loads of fire apparatus or that approved by the Fire Chief . 15 . 20 . 025 UFC Article 10 amended -- fire protection . Article 10 of the Uniform Fire Cods is amended by rewriting Sections 10 . 207 (g ) and 10 . 207 (m) ; by adding Secti.on 10 . 210 ; by rewriting Section 10 . 305 (a ) ; by adding Section 10 . 305 ( e) ; by rewriting Section 10 . 306 ; by adding Section 10 . 306 ( i ) ; by rewriting Section 10 . 309 � b ) and by adding Section 10 . 310 ( b) as follows : Section 10. 207 Turning Radius . (g ) The turning radius shall be no less than ninety-six ( 96 ' ) feet in diameter unless otherwise approved by the Fire ChieE . Sectim 10 , 207 Penalties . (m) The required width of the Fire Department access roadways skull not be obstructed in any manner , including the parking of vehicles . "ISO FARKTNG, FIRE LANE" signs or red painted curbs or other appropriate notice prohibiting obstructions shall be required and main- tained . Any obstruction or impedance to said Eire Lane may be cited, as ars infraction, or removed at the owner ' s expense, forthwith , by any public safety agency . Section 10 . 210 . Elevators . (a ) In all structures providing service to the general public which are to be equipped with an elevator or bank of elevators , the following skull be _10- required at the time of building con- struction : if only one elevator is pro- vided that elevator mint comply, and at least one elevator in each bank of elevators Shall be provided with a minimum clear distance between malls or between ;galls and door excluding return panels , not less than 80 inches by 54 laches , and a minimum distarnce from wall to return panel not less than 51 inches with a 42-inch side slide doer , unless otherwise designed to accommodate an ambulance-type stretcher 78 inches by 24 inches in the horizontal position . ( b) in buildings where more than one elevator is required to serve all floors , at least one elevator shall be equipped as Set forth in paragraph (a ) of this section . (c) Every building two or more stories in height must be provided with an elevator that meets the requirements of this code section. EXCEPTION : Group R, Divi- sion 3 occupancies are excepted Eram this section. Section 10 . 305(a ) . General . All fire extinguishing systems required by the provisions of this Code shall be designed and installed in accordance with the requirements of this Article b fire protection engineers and/or California licensed automatic fire sprinkler installation contractors . All fire hose threads used in connection with fire extinguishing systems shall be National Standard hose threads or as approved by the Fire Department . Section 10 . 305 ( e) . Automatic Dialing Devices . Automatic telephone dialing devices which transmit ars emergency alarm shall not be connected to the fire department emergency telephone number . -11- Section 10 . 306 . Automatic Fire- Extinguishing Systems . ( a ) Where Required . Every struc- turer except Group R, Division 3 and M-1 , hereafter canstructed, erected or moved onto a property , regardless of separation walls as outlined in Chapter 5 , Uniform Building r_oder and any struc- ture except for Group R, Division 3 and M-1, hereafter remodeled, rebuilt or renovated where such area increase exceeds fifty percent ( 50% ) of the original square footage as determined by the San Bernardino County Tax Assessor or 5. 0(10 square feet , whichever occurs first , shall have ars approved automatic sprinkler system installed throughout therein . ( b) Change of Occupancy . When there is a change of use or occupancy of a building which exceeds 5 , 000 square feet In floor area and which would place the building in a different division of the same group of occupancy or in a different group of occupancies , unless the proposed use is less hazardous , based on life or fire risk , than the existing use . ( c ) Where Required. Every Group R, Division 3 , structure hereafter con- structed , erected or moved onto a prop- erty, and any result of fire, earthquake, or other disaster which requires complete demolition and reconstruction of the structure, in its entirety, or a remodel exceeding fifty percent ( 50%) of the original square feet or 5 , 000 square feet , shall have an approved automatic sprinkler system installed throughout therein. (d ) Exceptions : ( 1 ) Outdoor , detached storage facilities of 200 square feet or less ( 2) Any work for which a building permit is not required _12_ ( 3 ) Block walls ( 4 ) Swimming pools and spas ( 5 ) Patio Covers : ( i ) All lattice Patio covers ( ii ) on existing houses , any patio that meets the definition of Chapter 49 of the Uniform Building Cade ( 6 ) Reroofing ( 7 ) Grading ( 8 ) Driveways ( 9) Satellite Dishes ( 10) Decks { i } Except a covered deck built as part of new house construction, ( 11 ) Gazebos ( 1 ) For special provisions on hazardous chemicals and magnesium, and calcium carbide, see Sections 10 . 301 and 45 . 209 and Articles 48 , 49 and 80 of the Uniform Fire Code. Section 10 . 306 . Automatic Fire- Extinguishing Systems . ( i ) Sprinkler System Standards ( 1 ) Every sprinkler system shall have at least one fire department connection. ( 2 ) Every sprinkler system shall incorporate backflow protection . ( 3 ) Past indicator valves and riser control valves shall be installed as determined by the Redlands Fire Department upon submission of plans . -13- ( 4 ) Sprinkler systems shall be designed to a working pressure of 150 psi and tested at 200 psi . ( 5 ) Minimum underground pipe size shall be six inches in diameter . Exception : Upon approval of the Redlands =i:e Department system riser may be of a 5mailer diameter . ( 6 ) Every sprinkler system shall be tested in accordance with the NFPA Standard Number 13-1583 . ( 7 ) The NFPA Standard Number 13 will be the acceptable standard used in the installation of all automatic fire sprinkler systems for occupancy Group A-B-E-H-I . The NFPA Standard Number 13D will be the acceptable standard for Group R, Division 3 occupancies . The AFPA Standard Number 13R will be the acceptable standard Eor occupancy in Group R. [division 1. . Where federal or state code regulations supersede local jurisdiction in whole or in part they shall only supersede that portion that applies . Section 10 . 309 ( b) . Where Required. Occuparncies having three ( 3 ) or fewer stories shall be required to have a Class 11 system. Occupancies having four ( 4 ) or more stories shall be required to have a Class E and 11 ( or III ) system. Section 10 . 310(b) . Where Required . Every building four ( 4 ) or more stories in height Shall be providad with no less than one ( 1 ) Class I standpipe for use during construCtion. Such standpipe shall be installed when the progress of con45truction i-5 not more than thirty ( 30 ) feet in height above grade. Such standpipe shall be provided with Fire -14 Department inlet connections at accessible locations adjacent to usable stairs . Such standpipe systems small be extended as construction progresses to within one ( 1 ) floor of the highast point of constructions having secured decking or flooring . In each floor there shall be provided a -1 inch valve outlet for Eire depart- ment use . Where construction heights require installation of Class 11 standpipe , fire pumps and water main connections shall be provided to serve the standpipe . - 15 . 20 . 030 UFC Article 11 amended -- general precautions against fire. Article 11 of the Uniform Fire Code is amended by rewriting Section 11 . 111 and by adding Section 11 . 204 ( b) as follows : Section 11. 111 . Chimney Spark Arrestors. ( a) Each chimney used in conjunc- tion with any fireplace , or any heating appliance in which solid or liquid fuel is used, shall be maintained with an approved spark arrestor . ( b ) An approved spark arrestor shall mean a device constructed in a workmanlike manner of stainless steel , aluminum, copper , brass , or woven galvanized wire mesh , nineteen ( 19 ) gauge minimum, with three-eighths ( 3/8" ) inch minimum to one-half ( 1/2" ) inch maximum openings, :Haunted in or over all outside flue openings , adequately sup- ported to prevent movement , and visible from the around. Sect-ion 11 . 204 : Flammable Decorative Materials . a15_ ( b ) Any person , company, or concern applying flame-prooting , fire retardant solution, or any other mate- rial , including Christmas trees , whether it be EOr a commercial , institutional , residential , or any other use , shall use a chemical Qr svlutiQn approved for such use by the Underwriters ' Laboratories, Inc. , or the Fite Marshal of the State. 15 . 20 . 032 UFC Article 1.4 amended -- fire alarm system. Article 14 of the Uniform Fire Code is amended by adding new definitions to Section 14. 102 ; by rewriting Sections 14 . 103 ( a) and 14 . 103 ( b) ; by adding Section 14 . 103 ( h ) ; by rewriting Sections 14 . 104 ( c) and 14. 105(a ) and by adding Sections 14. 105{ 6 ) , 14 . 105 ( e ) , 14 . 105( f) , 14 . 105 ( 9 ) and 14 . 108 ( b) as follows : Section 14 . 102 . Definitions . AUTOMATIC FIRE DETECTION SYSTEM is an approved system which automatically detects a fire condition and actuates a fire alarm signal device . AUTOMATIC FIRE EXTIt4GUISHING SYSTEM is an approved system of devices and equip- ment which automatically detects a fire and discharges an approved fire- extinguishing agent or water onto, or in the area of , a fire . Section 14 . 103 . General Requirements . (a ) Plans and Specifications . Complete plans and specifications of all fire alarm systems shall be submitted for rAvic,,w , approval and permit issuance prior to system installation. Plans and specifications shall include, but not be limited to, a floor plan, Location of a1L - initiating- and signaling devices , control- and trouble-signaling equip- ment , annunciations , power connection, -16- battery calculations , wiring types and sixes, post indicator values , sprinkler riser valves , and backflow preventor valves . Section 14 . 103 . General Requirements . ( b) System Design . All required fire alarm systems shall be installed, inspected and maintained in accordance with applicable National Fire Protection Association Standard Numbers 13 , 13D, 13R , 70 , 71 , 72A, 72C, 72E and 74 ; California Administrative Code , Title 19 and 24 ; California State Fire Marshal ' s Rules and Regulations; the Uniform Fire Code; the Uniform Building Code; and Redlands Fire Department Standards . Section 14 . 103 . General Requirements . ( h) Fees . Permit fees shall be paid prior to plans review. Section 14 . 104 . Required Installations . Cc ) Group R, Division 1 occupancies . Delete Exception 1 . Section 14 . 105 . Special Provisions . ( a) Monitoring. All required fire alarm systems shall be supervised by a U. L. -approved central , proprietary or remote station service or a local alarm which will give an audible signal at a constantly attended location . Section 14 . 105 . Special Provisions . ( d) Transmission . An approved automatic fire detection system or automatic fire extinguishing system shall transmit an alarm via two ( 2 ) dedicated phone lines from the protected premises to a location as specified in 14 . 105 ( x ) . EXCEPTION: The following need not comply with the above requirements . Automatic fire detection or fire extin- -17- quishing Systems not required to be monitored by this code or any other code or standard . ( e) Zoning . Zoning stall be required when any of the following exist . ( 1 ) Buildings over one story, or any building with a basement over 400 square feet , ( 2 ) Buildings with separate tenant areas . ( 3 ) Buildings over 17, 000 square feet in size . ( 4 ) Buildings with more than one sprinkler riser . ( 5 ) Buildings which require varying types of activating devices . ( ) Signals shall be designed to transmit at least the following information: ( i ) individual zone alarm signals when single or Multiple zones are required herein. ( ii ) A single alarm signal will be allowed when multiple zones are required herein, provided that Redlands Fire Department - approved visual means of zone indication is located at the protected premises , in a location approved by the Redlands Fire Department . ( f ) Alarm Reset Keys . A method shall be provided to reset the alarm system by fire department personnel . keys shall be installed in an approved lack box for all necessary operations , including alarm panel access . If remote reset capability is provided on the exterior of the building, remote key switch shall be of a type approved by the fire department . -is- (g ) Alarm Company Qualifications ( 1 ) No alarm company may install or service any fire alarm System unless issued a permit to do so under the provisions of this regulation , ( ) Alarm companies shall be listed with a fire department-approved , nationally recognized listing company that provides a listing service for installed fire alarm system( s ) . ( 3 ) Alarm company shall meet all requirements of National Fire Protection Association Standard dumber 71 and other related codes for the installation, supervision and mainte- nance of central, station supervisory services except as required by the Fire Prevention Bureau . ( 4 ) If the Fire Prevention Bureau determines that the applicant company conforms in all particulars to these requirements, the department shall grant such permit . A permit fee as determined by resolution shall accompany the application . ( 5 ) The Fire Chief shall have the power to suspend or revoke the permit , upon evidence satisfactory to the Fire Chief , of incompetence, willful or negligent fraud or failure to perform properly and effectively the duties assumed by the company issued the permit . Section 14 . 108 . False Alarms . (b) More than two ( 2 ) false alarms in a orae-( 1 ) month period of time or three ( 3 ) false alarms in any tato-{ 2 ) month period of time shall result in an assessment of fees for services provided by the Redlands Fire Department for all subsequent alarms in the remainder of the calendar year . _lg- 15 . 20 . 35 UFC Article 25 amended -- places of assembly . Article 25 of the Uniform Fire Code is amended by rewri.ing Sections 5 . 116 ( b ) ( ) ( K ) and 25 . 117 as follows : Section 25 . 116 ( b ) ( 2 ) ( K ) . Hand-held , flame-lighted candles shall not be permitted . Hattery-operated simulated candies may he used . Na permit is required for battery-operated candles or other electric candles . Section 25 . 117 . Standby Personnel . Whenever , in the opinion of the Chief , it is essential for public safety in any place of public assembly or any other place where people congregate , due to the number of persons ► or the nature of the performance , exhibition, display, contest or activity , the owner, agent or lessee shall employ one or more qualified firefighters, aS required and approved by the Fire Chief , to be on duty at such place. Said individuals shall be subject to the Fire Chief ' s orders at all times when so employed and shall be in uniform and remain on duty during the times such places are open to the public, or while such activity is being conducted. Before each perfor- mance or the start of such activity, said firefighters shall inspect all fire-extinguishing appliances provided to see that they are in proper place and in good working order , and shall keep diligent watch for fires during the time such place is open to the public or such activity is being conducted and take prompt measures for extinguishment of any fires that may occur . Qualified persons shall also perform, as required , emergency medical care . Such individ- uals shall not be required or permitted, while on duty, to perform any other duties than those herein specified . 15 . 20 . 40 UFC ' 9ection 61 . 106 ( c ) amended -- portable unvented ail-burning heating appliances. -20- Section 61 . 106( c ) of the Uniform Fire Code is amended to read as follows : Section b1 . 106 C } . Where Permitted . The use of listed portable unvented oil- burning heating appliances shall be limited to supplemental heating in Group B and M Occupancies . EXCEPTION: Upon approval of the Eire Chief , portable unvented oil- burning heating appliances may be permitted in any occupancy during the construction process when such use is necessary for construction and the use does not represent a hazard to life or property. 15 . 20 . 042 UFC Article 77 amended -- explosives and blasting agents . Article 77 of the Uniform Fire Code is amended by adding Section 77 . 106 ( e ) as follows : ( e ) The storage of explosives and blasting agents is prohibited as follows : ' All areas and zones , unless special approval is granted by the City Council of the City of Redlands . " 15 . 20 . 045 UFC Article 79 amended -- flammable and combustible liquids . Article 79 of the Uniform Fire Code is amended by adding Section 79 . 115 ( d ) (A) ( iv) ; by rewriting Sections 79 . 501 , 79 . 507 ( c) ( 4 ) (A) , 79 . 603 and 79.1206 and by adding Section 70 . 1401 (x ) as follows : -21- Section 79 . 115 Mariner of 'nesting . (d ) (A) ( iv) Any tank which has been out of service for more than 90 days shall he pressure tested, at the design pressure of the tank , for 30 minutes . The test shall be performed using water . Tests With product ( s ) are prohibited. Section 79 . 501 . Limits _ (a ) The storage of Class I and Class II liquids in above-ground tanks outside of buildings is not allowed except in remote, undeveloped locations as determined by the Fire Chief . Out- side above-ground tanks are prohibited in all commercial areas , developed residential areas , and other areas where the Fire Chief heaving jurisdiction determines that the installation of flamable and combustible aboveground storage tanks will create a hazard to occupants and property owners in the area . The liquid capacity of any one tank shall not exceed 2 , 000 gallons and in no case shall the aggregate capacitor at any one site exceed 3 , 000 gallons . ( b) No neer bulk plants shall be constructed within any principal business district or in any closely built commercial or heavily populated areas as such districts or areas shall be designated by the Fire Chief . ( c) Waste oil disposal . ( i ) Crank case drainings . Tanks installed for crank case drainings shall be installed in accordance with the requirements for Class I liquid storage . In addition thereto, drainage lines terminating inside a building shall be equipped with a non-removal- type cap ( such as a hinged cap) . ( ii ) stozage . Crank case drainings and waste oil products may be stored in an above-ground tank as -22- approved by the Fire Chief . Drainings and used oils may also be stored outside a building in not more than three tight drums having an aggregate capacity not exceeding IaO gallons , or in tanks having an aggregate capacity not to exceed 1 , 100 gallons and in no case shall any one tank exceed a 600 gal'.16on capacity . Section 79 - 507 ( c) ( 4 ) (A) . Where the average height of the dike containing Class l and Class II liquids is over 12 feet measured from interior grade , or where the distance between any tank and the top inside edge of the dike wall is less than the height of the dike wall , provisions shall be made for normal operation of valves and for access to tank roof ( s ) without entering below the top of tete dike . These provisions may be met through the use of remote oper- ated valves , elevated wal� ways or similar arrangements . Section 79 . 603 . All underground tanks and piping shall be protected from corrosive conditions in accordance with the requirements established by the Environmental Health Services Department of San Bernardino County . Section 79. 1206. (a) Parking on Thoroughfare . Any vehicle containing hazardous materials shall not be left unattended on any residential street nor in or within five hundred ( 500 ) feet of any residential area , apartment or hotel complex , or any education, hospital or care facility at any time , or at any other place that would , in the opinion of the Chief , present an extreme life hazard. Its locations oth@r than those specified in Section 80 . 112(a) , a driver shall not leave the vehicle unattended on any street , highway, avenue or alley . -23- EXCEPTIONS: 1 . The necessary absence in connection with loading or unloading the vehicle, but during actual discharge Ecom the vehicle , the provisions of Section 80 . 112 ( b ) shall apply . 2 . Stopz for meals during the day or night , if the street is well lighted at the poinc of parking. 3 . When, in the case of breakdown or other emergency, the operator must leave the vehicle to take necessary action to correct the emel-gency. ( h) parking Off Thoroughfare . A tank vehicle shall not be left unat- tended within five hundred ( 500 ) feet of any residential area , apartment or hotel complex, or any educational, hospital or care facility at any time ; or at any other place that would, in the opinion of the Chief, present an extreme life hazard. A tank vehicle shall not be parked at any one point for longer than one hour except : 1 . Off a Street , highway, avenue or alley; . Inside a bubo plant and twenty-five ( 25 ) feet from the property line or within a building approved for such use. 3 . At any other approved location not less than fifty ( 50 ) feet from any building except those approved for the storage or servicing of such vehicle ; 4 . Wheft, in case of breakdown or other emercgency, the operator must leave the vehicle to take necessary action to correct the emergency, -24- Cc;) Garaging . Vehicles containing hazardous materials shall not be parked or garaged in any buildings other than those specifically approved for such use by the Chief . Section 79 . 1401 ( a ) No new bulk plants Shall be constructed within any principal business district or in any closely built commercial or heavily populated areas as such districts or areas shall be designed by the Fire Chief . 15 . 20 . 055 UFC Section 82 . 104 amended -- location of containers . Section 82 . 104 of the Uniform Fire Cade is amended by adding Section 82 . 1O4 ( e) as follows : Section 92 . 104 (e ) . Liquified petroleum gas containers and tanks shall be posi- tioned in relation to one another in such a manner so that the length axis of each tank is parallel to that of other tanks . 15 . 20 . 060 UFC Section 85 . 104 amended -- abatement of electrical hazards. Section 85 . 104 of the Uniform Fire Code is amended to read as follows : Section 85 . 104 . it shall be unlawful to maintain any electrical wiring , appliance, apparatus, or device in violation of the National Electrical Code . When any electrical hazards are identified, appropriate measures to abate such conditions shall be taken . -25- 15 . 20 , 065 UFC Appendix I-A amended -- life safety require- ments for existing buildings other than high rise . Appendix I-A of the Uniform Code is amended by rewriting Sections 1 (a ) , 1 ( b ) and 6 as follows : Section l (a ) . Purpose . The purpose of this appendix is to provide a reasonable degree of safety to persons occupying existing buildings that do not conform with the requirements of this Code by providing for alterations to such existing buildings . Section 1 (b) . Application . The provisions of this Appendix shall apply to the alteration of any unsprinklered existing building exceeding 5 , 000 square feet in an area as specified in Section 15 . 04 . 070 of the Redlands Municipal Code . EXCEPTION: Group M is excepted from all provisions of this appendix . Section 6 . Smoke Detectors . Every dwelling unit in an apartment house and every quest room in a hotel , motel , or lodging house fall R-1 group occupan- cies) used for sleeping purposes shall he providad with smoke detectors . In dwelling units, smoke detectors shall be mounted on the ceiling or wall at a point centrally located in the corridor or area giving access to rooms used for sleeping purposes . In efficient dwell- ing units, hotel sleeping rooms , and hotel suites , smoke detectors shall be centrally located on the ceiling of the main room or hotel sleeping room. Where sleeping raams are on an upper level , smoke detectors shall be placed at the center of the ceiling directly above the stairway . All smoke detectors shall conform to the Uniform Building Code Sta' dard No. 43-6 and shall be located in accordance with approved manufac- turers instructions . When actuated, -26- each detector shall provide an alarm in a dwelling unit or guest room. Smoke detectors may be battery operated when installed in existing buildings . A smoke detector shall be installed in the basement of dwelling units having a stairway which opens from the basement into a dwelling . Such detector shall be connected to a sounding device or othe detector to provide an alarm which will be audible in the sleeping area. 15 . 20 . 067 UFC Appendix I-B amended R- life safety require- ments for existing high rise buildings . Appendix I-D of the Uniform Fire Cade is amended and entirely rewritten as follows : Section 1 . Intent . (a ) It is the intent of this Chapter to prescribe regulations , consistent with nationally recognized goad practice , for safeguarding , to a reasonable degree of life and fire safety, buildings designed for human occupancy which exceed forty-five ( 45 ) feet in height . ( h ) Where no specific standards or requirements are specified in this Chapter , or contained within other applicable laws , adopted codes or ordinances, compliance with the standards of the American Insurance Association, Factory Mutual Engineering, the National Fire Protection Association, or other nationally recognized fire safety standards as are approved by the Fire Chief and Building Official , shall be deemed prima facie evidence of compliance with this intent . Section 2 . Definitions . ( a ) For - the purpose of this Chapter , a "high-rise building" shall mean any building used for human -27- occupancy which exceeds forty-five ( 45 ) feet or three ( 3 ) stories rn height above the lowest level of approved fire department vehicle access or other physical configuration that qualifies a building as high rise by local ordinance . ( b) For tete purpose of this Chapter , "building access" shall mean ars exterior door opening conforming to all of the following ; ( 1 ) Suitable and available Ear fire department use; ( 2 ) Located at grade level ; ( 3 ) T'eading to a spacer room or area having foot traffic communication capabilities with the remainder of the building; and ( 4 ) Designed to permit penetration through the use of fire department forcible entry tools and equipment unless other approved arrangements have been made with the fire authority having jurisdiction. ( c ) For the purpose of this Chapter , "bank of elevators" skull mean a group of elevators or a single elevator controlled by a common ope.-- ating system; that is , all those e}evators which respond to a single call button constitute a bank of elevators . There is no limit an the number of cars which may be in a bank or group, but there may be not more than four ( 4 ) cars within a common hoistway. (d ) For the purpose of this Chapter , a '*fire control center " skull mean a ventral location within ttie high- rise building for fire department operations and monitoring of such systems and equipment as required in this. Chapter . - 8- Section 3 . Scope. (a ) Every high-rise building here- after constructed shall conform to Section 5 , through and including SAction 1 (b) and Section 17 of this Chapter . ( b ) Every high-rise building hereafter constructed skull conform to all provisions of this Chapter . Section 4 . Uniform Building Cade . Whenever the Uniform Building Code is references , it shall refer to the latest edition adopted by the City council . Section S . Aut-omatic Sprinkler System. (a ) Every high-rise building shall be provided with an automatic fire sprinkler system. ( b ) The fire sprinkler system shall conform to National Fire Protection Association Standard Number l3 and the following- ( 1 ) The NFPA Standard Number 13 used shall he the latest edition; ( 2 ) Shutoff valves and grater flow devices shall be provided for each floor . In addition to actuating a local alarm on the floor upon which the Mater flow is detected , operation of such values shall transmit an alarm to a U.L.-certified central receiving station and to the fire control center if the fire control center is required by other sections of this Chapter ; ( 1 ) System piping shall be hydraulically designed to the following standards : ' ( i ) Light Hazard occupancies as defined in Appendix A of NFFA Standard Number 13 . - Ordinary Hazard , Group 1 Density Curve; -29- ( ii ) Ordinary Hazard Occupancies (Group l ) as defined in Appendix A of NFPA Standard dumber 13 . - Ordinary Hazard , Group 2 Density Curve, ( iii ) Ordinary Hazard Occupancies (Group 2 ) as defined in Appendix A of NFPA Standard dumber 13 . - Ordinary Hazard, Group 3 Density Curve; ( iv) Ordinary Hazard Occupancies (Group 3 ) as defined in Appendix A of NFPA Standard Number 13 . R Extra Hazard, Group 1 Density Curve: ( v ) Extra Hazard Occupancies (Groups 1 or 2 ) as defined in Appendix A of NPPA Standard Number 13 . - Extra Hazard, Group 2 Density Curve. ( 4 ) Any room or area of the building where the application of water is considered undesirable, or may complicate fire fighting or rescue attempts, may have the sprinklers deleted if alternative extinguishing systems are installed . Such rooms or areas may include : ( i ) Generator , transformer and computer rooms ; ( ii ) Safe deposit or other vaults of fire-resistive construction , when used for the storage of records, files , and other documents when stored in metal cabinets or on metal shelving; ( iii ) All ccmmL�nications equipment areas ; ( iv) Other areas with specific prior approval from the Fire Chief, Fire Marshall and Building official based on a review of justifi- able~ fire protection engineering criteria . -30- ( 5 ) The actuation of any sprinkler head shall : ( i ) Operate the voice alarm system, and nhall place into operation all equipment necessary to prevent the recirculation of smoke ; ( ii ) Transmit ars alarm directly to a U.L . -certified central receiving statLon and to the fire control center if the fire control center is required by other sections of this Chapter . Such signal shall be zoned with a minimum cf one ( 1 ) zone per floor and a maximum of ten thousand ( 10 , 000 ) square feet per zone . 9ectian 6 . Alarm and Communications . (a ) Every hi-gh-rise Building shall have manual fire alarm boxes , which shall be located adjacent to exits into corridors , stairway shafts, and in every elevator lobby, and shall : ( 1 ) Operate the voice alarm system, and place into operation all equipment necessary to prevent the recirculation of smoke; ( 2 ) Transmit an alarm directly to a U. L. - certified central veceiving station and to the fire control center if the fire control center is required by other sections of this chapter . Such signal shall be zoned with a minimum of one ( 1 ) zone per flour and a maximum of ten thousand ( 10, 0G0 ) square feet per zone, ( 3) A radio antenna system shall be installed on the interior or exterior of said high rise to allow the use of portable hand held radios by the Fire Department . ( b) 'Three ( 3 ) commc n i ca t i on systems shall be provided as follows ; -31- ( 1 ) Voice alarm system . The operation of any smoke detector , sprinkler , water flow device or manual fire alarm station shall automatically sound an alert signal to the desired areas followed by voice instructions giving appropriate information and direction to the occupants . ( i ) The fire control center , when required by other sections of this Chapter , shall contain controls for the voice alarm system sc that a selective or general voice alarm may be manually initiated; ( ii ) The system shall be supervised to cause the activation to an audible trouble signal to a U.L . - certified central receiving station and to the fire control Center if the fire control center is required by other sections of this Chapter upon interruption or failure of the audio path including amplifiers , speaker wiring , switches and electrical contacts , and shall detect opens, shorts and grounds , and any other malfunction which might impalr the transmission of voice alarms; ( iii ) The alarm shall be designed to be heard clearly by all occupants within the building or designated portions thereof as is required for the public address system. Said alarm will be subject to field audibility tests ; ( iv) This system shall be capable of fire department inter- communication with units selectable Erom the Eire control center or other designated location. ( 2 ) Public address system. The • public address system shall be a one-way system providing communication from the fire control center or other -32- designated location to tete following loca t i oris : ( i ) Elevators , elevator lobbies , corridors and stairways . Speakers in corridors shall be located not more than two hundred ( 200 ) feet apart, and shall be subject to field audibility tests ; ( ii ) In every room exceeding one thousand ( 1 ,000 ) square feet in area; ( iii ) In every room, exceeding fifty ( 50 ) occupant load; ( iv) rn each dwelling unit or hotel guest room. ( 3 ) Fire Department System. A sound powered telephone system capable of communication between all floors and with the Eire control center or other designated location shall be provided. All exterior phone jacks shall be designed to communicate with the fire control center , or other designated locations , and all other areas of the building . An acceptable number of hand- held phare sets as determined by the fire department shall be mace available and stored at the fire control center and/or other locations as specified by the Fire Chief . Sound-powered phone equipment , including commuriiCation s panel, phone sets and location of phone jacks, are subject to fire department approval . Phone jacks shall be located as follows : ( i ) At every floor level at each hose Cabinet ; ( ii ) At every exterior location where a stair shaft exists to a public way; ( iii ) At the exterior of each stair shaft penthouse located on the roof ; -33- ( iv) In every elevator ; ( v) At every elevator lobby: (vi ) In every meehanicai control center ; ( vii ) In every air handling equipment room; ( viii ) Iri every elevator machinery room; ( ix ) At the emergency heliport or other approved roof locations; (x ) And other locations as deemed necessary by the Fire Chief and Building Official . ( c ) The sounding of a fire alarm signal in any given area or floor shall not prohibit voice communication to other areas or floors . ( d ) The voice alarm and public address system may be combined. Combination systems shall be designed to permit voice transmission to override the fire alarm signal , but not discon- tinue the fire alarm signals as provided at the fire control center or other designated locations . (e ) The alarm and communication systems shall be designed and installed so that interruption of any single speaker shall not cause a loss of any other speakers in the circuit . Section 7 . Smoke Detection . ( a) Every high-rise building shall be protected with an approved , electri- cally supervised, automatic fare detec- tion. system having detectors which will respond to visible or invisible products OE combustion in the following locations ; -34- ( 1 ) in every mechanical equipment room; ( 2 ) in every heating , air condition.ing or ventilation duct system as follows : { i } in the main circu- lating air duct on the downstream side of the filters and so located as to operate in case of smoke in the air stream, or such devices may be installed in each room or space served by a return air duct ; ( ii ) At every opening through any assembler having fire- resistive rating of two ( ) hours or more , ( 3 ) In every elevator lobby . � b) The actuation of any smoke detector shall ; ( 1 ) Operate the voice alarm system, and place into operation all equipment necessary to prevent the recirculation; of smoke; ( 2 ) Transmit an alarm directly to a U. L. certified central receiving station and to the fire control center if the fire control center is required by other sections of this Chapter , and shall be on a separate zone. Section; 8 . Smoke Control . (a ) Every high-rise building shall have mechanical ventilation for the removal of the products of combustion provided in every story and it shall consist of mechanical air handling equipment designed to accomplish smoke removal . Under fire conditions, and return and exhaust air shall be moved directly to the outside without recirculation to other sections of the _35r building . The air-handling system shall provide a minimum of one ( 1 ) exhaust air change each ten ( 10 ) minutes for the largest single room. ( b) Additional ventilation for the removal of the products of combustion shall be provided in every story and shall consist of one ( 1 ) of the following : ( 1 ) Panels or windows in the exterior wall , which can be opened from the inside and from the fire control center or other approved locations , shall be provided at the rate of at least twenty ( 20 ) square feet per fifty ( 50 ) lineal feet of exterior wall in each story and dintrihuted around the perimeter at not more than fifty ( 50 ) foot intervals . The openable panels shall be tempered glass . Such panels shall be clearly identified as required by the fire department ; ( ) Any other engineered design which will produce equivalent results as certified for approval to the Fire Chief by a registered Fire Protectlon Engineer . Section 9 Elevators . (a ) Elevators and elevator lobbies in all high-rise building shall comply with Chapter 51 of the Uniform Building Code and the following : ( 1 ) On every floor except the main entrance level , the elevator lobby shall be provided with self-closing twenty ( 20 ) minute minimum rated fire doors to form a vestibule . Said doors shall close automatically when the smoke detector in the lobby is activated . Both sides of the doors shall have sign reading " IN FIRE EMERGENCY , DO NOT USE ELEVATOR --- USE EXIT STAIRS" in two ( 2) inch• high three-fourths ( 34) inch stroke letters and a map on the floor showing the locations where the person -36- is and the path to the closest exit stairs ; ( 2 ) A permanent sign shall be installed in each elevator cab adjacent to the floor status indicator and at each elevator call station on each floor reading "IN FIRE EMERGENCY, DO NOT USE ELEVATOR --- USE EXIT STAIRS" in one- half ( 12 ) inch high one-eighth ( 18 ) inch wide atroke letters or similar verbiage approved by the Fire Chief and Building official; ( 3 ) Elevator hoistways shall not be vented through an elevator machine room. Cable slots entering the machine room shall be sleeved beneath the machine room floor artd extend to not less than twelve ( 1 ) inches below the shaft vent to inhibit the passage of smoke into the machine room; ( 4 ) At least one ( 1 ) elevator car in each bank serving all floors shall have a minimum inside car platform of four { 4) feet six ( 6 ) inches deep, by six ( 6) feet eight ( 8) inches wide , with a minimum clear opening width of forty- two ( 42) inches, unless otherwise designed and approved to provide equivalent utility to accommodate an ambulance stretcher having a minimum size of twenty-four ( 4 ) inches by seventy-eight ( 78 ) inches, in its horizontal position . This elevator shall be identified . Section 10 . Standby and Emergency Power and Lighting . (a) Every high-rise building shall be provided with a standby power system as follows : � 1 ) An on-site standby power generation system consisting of one ( 1 ) or more generators . In the event of failure of the normal source of electric service ► the standby power generation system shall provide an alternate source of electrical energy to serve at least the designated power loads set forth in subsection ( ) below; -37- ( ) The power load requirements for sizing the standby power generation system shall include, but not necessarily be limited to, the following : ( i ) Exit signs and exit illumination as required by Section 3312 of the Uniform Building Code ; ( ii ) Elevator car lighting circuits ,- ( iii ) ircuits ;( iii ) Fire alarm system; ( iv) Eire detection system; ( v) Sprinkler alarm system; (vi ) Electric-driven fire Pumps: (vii ) Voice communication systems ; ( viii ) Mechanical ventilation and air handling equipment required by this section; ( ix) Elevators assigned for fire department use; (x) All public assembly areas shall have lighting in accordance with exit illumination as required in Section 3313 of the Uniform Building Code ; (xi ) All parking garages shall have lighting in accordance with exit illumination as required in Section 3313 of the Uniform Building Code ; ( xii ) Lighting circuits supplying elevator lobbies , the fire control center , and the generator room. ( 3 ) The standby power genera- tion system shall be equipped with suit- -38- able means for automatically starting the generator set ( s ) uporn failure of the normal electrical service, and shall protide for the automatic transfer and operation of electrical syst4ms and equipment specified above , at full cower within sixty ( 60 ) seconds of such normal service Eailure; ( 4 ) On-site fuel supplies for prime movers of standby power generator sets shall be sufficient for at least six ( 5 ) hours at full demand opera- tion . Where fife pumps are required , an eight ( 8 ) hour fuel supply shall be provided . ( b) Every high-rise building shall he provided with emergency electrical systems as follows = ( 1 ) Electrical systems and equipment specified herein are classed as emergency systems . ( i ) Exit signs and exit illumination as required by Section 3313 of the Uniform Building Code ; ( ii ) Elevator car lighting circuits : ( iii ) Fire alarm system; ( iv) Fire detection system; (v) Sprinkler alarm system. ( 2 ) The emergency power supply system shall be so designed that upon Failure of the normal electrical systems and equipment specified above, it shah, be automatically transferred without power interruption. Such emer- gency power supply may be separate from the standby power specified above . ( c) When the standby power genera- tion system reaches full operating -39- capacity, the emergency electrical systems and equipment shall be trans- ferred thereto. ectLon 11 . Siesmic Considerations . ( a ) Every high-rise building Shall have the anchorage of the following mechanical and electrical equipment designed and installed in accordance with Section 2312 of the Uniform Building Code for lateral force based on a Cp value of 4 . 5 unle$s data substan- tiating a lesser value is furnished : ( 1 ) Elevator drive and suspension systems ; ( 2 ) Standby power and lighting facilities ; ( 3 ) Fire Pumps, automatic fire extinguishing systems and other fire protection equipment ; ( 4 ) Air handling equipment regulated by this Chapter . verification of such conformance shall be substantiated by a licensed structural engineer . Section 12 . Spandrel Protection . (a ) Every high-rise building shall have spandrel protection provided by one of the following : ( 1 ) Openings in exterior walls , where such openings are within five ( 5 ) feet of each other horizontally on vertically adjacent floors , shell be protected by approved flame barriers either extending thirty ( 30 ) inches beyond the exterior wall in the plane of the floor or by approved vertical panels not less than three ( 3 ) feet in height above the Eloar ; { 2 ) Decrease the spacing of sprinkler heads on the perimeter , or in -40- any vocations where spandrels would be required, to that as specified for extra hazard occupancies in National Fire Prevention Association Pamphlet Number 13 ; ( 3 ) Alternate spandrel fire protection may he considered subject to approval of the Fire Chief and Building Official when designed and submitted by a Fire Protection Engineer . Seckion 13 . Fire Fighting Provisions . (a ) Every high—rise building shall have each floor of the building provided with Eire department cabinets . The cabinets shall be as close as possible to each exit into corridors, stairway shafts , and in every elevator lobby, and shall provide accessibility only to the fire department and ort-site fire brigade. The cabinet and all equipment specified in this section shall conform to fire department standards . Operation of doors to fire department cabinets shall activate signals in a U .L .- certified central receiving station and in the fire control center if the fire Control center is required by other sections of this Chapter . Contents of the cabinet shall be : ( 1 ) One ( 1 ) two and one-half ( 2-1/2 ) inch to one and one-half ( 1-12 ) inch grated Wye connected to the standpipe ; ( 2 ) Two hundred ( 200) Eeet of one and three--quarter � 1-3/4 ) inch , four hundred ( 400 ) pound test , fire hose line: one hundred ( 100 ) feet pre- connected to the gated wye, one hundred ( .100) feet rolled . ( b) On the roof level , fire department cabinets as described in " ( a ) " above shall be located to provide fire hose lines within thirty ( 30 ) feet of all areas of the roof . -41- ( c) Tt%ere must be arse ( 1 ) "crash cart" of fire department tools . The crash cart , when fuller equipped, shall fit into the elevators , shall be dAgigned tO fire depaztMeftt standards , and shall contain the following standard fire control and rescue provisions : ( 1 ) Halligan tool ; ( 2 ) Pry bar ; ( 3 ) Pick-head aster ( 4 ) Four ( 4 ) sprinkler shut- offs ; ( 5 ) Telescoping pole with which to apply sprinkler shut-offs ; (6) Twelve ( 12) rubber door holders : ( 7 ) Six ( 6 ) marking pens for search and rescue ; ( 8 ) One hundred ( 100 ) feet to two and orae-half ( 2-12 ) inch, four hundred { 400 } pound test , fire hose line, ger fire department Specificati Section 14 . Automatic Sprinkler Systems . (a ) Every high-rise building in excess of seventy-five ( 75 ) feet above the lowest level of approved fire department vehicle access or other physical configuration that qualifies a building as high rise by local ordinance shall also conform to the following additional automatic sprinkler system requirements; ( 1 ) A minimum of two ( 2 ) fire pumps independently driven shall be provided , each sized for the sprinkler demand and for an additional minimum five hundred ( 50Q ) gallons per minute for fire department standpipe operations . One of the pumps shall be electrically driven and the other pump small be diesel fuel operated ; ( 2 ) In addition to the mairt nater supply, a secondary on-site supply of water equal to tete hydraulically calculated sprinkler design demand, plus five hundred ( 500 ) gallons per minute additional for the total standpipe system, shall be provided . This supply shall be automatically available if the principal supply fails , and shall have a duration of thirty ( 30 ) minutes . The on-site supply of water as indicated above shall be maintained in a separate system from the public domestic water system, and shall conform to all applicable crass�coanection requirements of the City Engineer ' s Office. Section 15. Fire Control Center . (a ) Every high-rise building in excess of selvanty-figs ( 75 ) feet abavLb the lowest level of approved fire department vehicle access or other physical configurarion that qualifies a buia-dims a high rise by local ordinance shall be provided with a fire control center located near or adjacent to the -43- main entrance to the building or at any location approved by the Fire Chief and Building Official . The fare control center shall be directly accessible from the outside of the building , consistent with standards developed by the Fire Chief and Building Official . The Eire control center shall be designed to accommodate the functional control and command personnel required to conduct an emergency activity . There shall be a minimum net floor area of two hundred fifty ( 25G ) square feet . This floor area shall not be encumbered upon by any ;rails , equipment , or other appurtenances necessary to the function of the roam. The Eire control center shall be separated from the remainder of the building by not less than two ( 2 ) hour fire-resistive construction with all Openings protected by assemblies having a fire-resistive rating of not less than one and one-half ( 1-112 ) hours . The fire control, center shall be used to house the Eollowing equipment : ( 1 ) Voice comrnunicat ion control equipment including equipment necessary to the function of the control unit and their display and status panels . ( 2) Fire alarm and fire detection control equipment including equipment -necessary to the function of the control unit and their display and status panels ; ( 3 ) Status indicators and controls for elevators; ( 4 ) Air handling system status indicators and control switches . ( 5 ) Controls for unlocking stairway doors and status board indicating whether said doors are locked or unlocked ; -44- ( b ) Sprinkler valve supervision and water flow detector display panels ; ( 7 ) Alaem, water flog, and trouble signals shall be annunciated by means of an audible signal and a visual displays which indicates the building, floor , zone or other designated area from which the alarm, water flow or trouble signal. originated ; ( 8) Standby power status display and controls; ( 9 ) A telephone connected to the public telephone system adjacent to the fire department communication systems . This telephone to be for express use of the fire department . Telephones for building occupant Esse shall be separate; ( 10 ) Intercom to exterior of fire control center to allow for verbal communication without opening the door ; ( 11) Supervision indicator of the fire department cabinets; ( 12 ) Three ( 3 ) certified copies of the building floor plans , mechanical plans, an electrical plans ; ( 1 3 ) Three ( 3 ) copies of the fire department pre-plans ; ( 14 ) Other fire protection equipment and systems controls, such as : ( i. ) dater tank level indicators; ( ii ) Pira pump controls and status indicators ; ( iii ) Fire level indicator on -auxiliary geneeators and fire pumps . -45- ( 15 ) Ariy other siallar equipment , controls , or status indica- tors as deemed necessary by the Fire Chief and Building Official . ( b) Any equipment that is a status indicator shall be in the form of a graphic annunciator . The graphic annunciator shall be a line diagram of the building with the lights and activation switches in proper perspec- tive on the diagram. The graphic annunciator shall be further keyed to the required building floor plans per floor and location cn the floor . (c ) As well as the graphic annunciator , an alpha-numeric printout of all staters indications or switch activations , along with the date and time of alarm or activation, stall be provided . This printout shall also be coded to provide the location of the activation on the building floor plans per floor and location of the floor . (d ) The fire control center shall not be used for the housing of any boiler , heating unit , generator , or storage . Section 16 . Emergency Helicopter Land- ing Facility. (a ) Each high-rise building, in excess of seventy-five ( 75 ) feet above the lowest level of approved fire department vehicle access or other physical configuration - that qualifies building a high rise by local ordinance shall incorporate ars emergency heli- copter landing facility located an the roof of the building in an area approved by the fire department . ( 1 ) A landing glide slope angle determined by a ratio of eight ( 8 ) feet horizontal distance for every one ( 1 )' foct of vertical clearance required . Two ( 2 ) such approaches shall be avail- able at least ninety ( 90 ) degrees removed from each other ; -46- ( 2 ) A clear , unobstructed landing and takeoff area with a minimum dimension of one hundred ( 100) feet by one hundred ( 100 ) feet and a reinforced touchdown area having a minimum dimen- sion of fifty ( 50 ) feet by fifty ( 50 ) feet ; ( 3 ) If the roof has no parapet wall , a substantial fence or safe�_y net shall be provided around the perimeter of the roof in such a manner that it will not restrict or reduce the required landing and takeoff area; ( 4 ) A wind-indicating device shall be provided; ( 5 ) The roof top shall be marked by an emergency marker as required by the Chief of the fire department ; ( 6 ) The roof tap shall be marked with the numerical street address of the building, with the numbers facing the street frontage corresponding to the address . The size of the numbers are to be three ( 3 ) feet high and one ( 1 ) foot wide. Section 17 . plan Review and Update. (a) Whenever there are practical difficulties in strict application of these provisions, the Fire Chief and Building Official may modify the provi- sions upon application, in writing, by the owner , lessee, developer or lois authorized representative, complied with and the public safety secured . Particu- lars of any such modification or devia- tion from these provisions , when granted Or allowed, shall be rendered by a written decision of the Fire Chief and Building Official and entered upon the record of the City with a signed copy furnished to the appellant . -47- ( b) The Fire Chief and Building Official , with notice to the appellant , may approve any alternate material or rftethod , provided that they fired that the proposed des ign$ use# or operation satisfactorily complies with the latent OE these provisions and that the materials , methods of work performed, or operations to be employed are, for the purpose intended , at least equivalent or that prescribed by these provisions in quality, strength, effectiveness , fire resistance, durability, and safety . ( c) The Fire Chief and, Building Official may require tests as proof of compliance with the intent of these provisions or alternates thereto tc be made by an approved agency at tree expense of the person or persons requesting approval of alternate methods , materials , or operations . (d) If technical expertise is unavailable within the Fire or Building Departments because of new technology, products , process, facilities , materials and uses attending design, operation or use of a Building or premises subject to the provisions herein contained, the Fire Chief and Building official may require the appellant or his authorized representative to provide, without charge to the City cf Redlands , a technical opinion and report prepared by a qualified engineer , specialist , laboratory or fire safety specialty organization acceptable to the Fire Chief, Building . Official , and the appellant , to thoroughly analyze the fire safety properties of said design , operations , or use in prescription, approval and adoption of the necessary recommend changes . (e) There shall be , and here is , created a Board of Appeals . in the event that the Fire Chief and Suildirig Official deny an appeal after considera- tion of all provisions of this section , the appellant may f u r the r appeal to the -48- Board of Appeals as a final authority on the issues . The Board of Appeals shall consist of five members who are quali- fied by experience and training to pass upon perttihent matters . The Fire Chief and Building Official shall be ex officio members , one of which shall act as Secretary of the Board . The Board of Appeals shall be appointed by the City Council and shall hold office at their pleasure . The Board shall adopt reasonable rules and regulations for conducting its investigations and shall render all decisions and findings in writing to the Fire Chief and Building Official , with a duplicate copy to the appellant , and may recommend to the City Council such new legislation as is consistent therewith. ( f ) The appellant may appeal any action of the Board of Appeals to the City Council . 15 . 20 . 070 UFC Appendix li-A amended -- suppression and control of hazardous fire areas . Section 7 of Appendix 11—A of the Uniform Fire Code is amended to read as follows : 7 . Spark Arresters Required . ( a) Each chutney used in conjunction with any fireplace or any heating appliance in which solid or liquid fuel is used shall be maintained with an approved spark arrrester . ( b) An approved spark arrester shall mean a device constructed of stainless steel , aluminum, copper or brass , woven galvanized wire mesh, nineteen ( 19 ) gauge minimum, with three- eighths ( 38 ) inch minimum to ane-half ( l 2 ) inch maximum openings , mounted in or over all outside flue openings in a vertical or near vertical. position, adequately supported tc prevent movement and visible from the ground . -49- 15 . 20 . 075 Limits of districts in which storage of combust- ible liquids is prohibited. A. The limits referred to in Section 79 . 501 and 79 . 1001 of the Uniform Fire Code in which stcragia of Flammable or combustible liquids in aboveground tanks is prohibited are hereby established as follows : Not permitted without specific authorization in writing from the Chief of the Fire Department . B. The establishment of new bulk plants for the storage or blending of flammable or combustible liquids shall not be permitted except as specified in Sections 18 . 112 . 030 and 18 . 116 . 030 of this code. 15 . 20 . 076 Limits of districts in which bulk storage of liquified petroleum gas is restricted. The limits referred to in Section 8 . 105 (a ) of the Uniform Fire Code in which bulk storage of liquified petroleum gas is restricted are established as follows - Not permitted without specific authorization in writing from the Chief of the Fire Department . 15 . 20. 077 Limits of distances in which storage of explosives and blaring agents is prohibited . The limits referred to in Section 77 . 106 {b} of the Uniform Fire Code in which storage of explosives and _so_ blasting agents is prohibited are established as follows : Not permitted without specific authorization in writing from the Chief of the Fire department . 15 . 20 . 084 Permit requirements and appeals . Khenever the Chief shall disapprove an application or refuse to grant a permit applied for , or when 2Lt is claimed that the provisions of the Code have been miscon- strued or wrongly interpreted, the applicant may appeal from the decision of the Chief to the City Council within thirty ( 30 ) days from the date of the decision being appealed. 15 . 20 . 090 New materials , processes or occupancies which may require permits. The City Manager , the Chief and the Chief of the Division of Fire Prevention shall act as a carnmittee to determine and specify, after giving affected persons an opportunity to be heard, any new materials , processes or occupancies which shall require permits , in addition to those now enumerated in - the Code . The Chief of the Dkvisior� of Fire Prevention shall post such list in a conspicuous place in his office , and distribute copies thereof to interested persons . 15 . 20 . 100 Enforcement-Fire Chief authority. 51- It is the duty of the Fire Chief, his designated representatives , and the officers of the Fire Prevention Bureau within the Fire Department to interpret and enforce the provisions of the Uniform Fire Code and tete arniandments thereto. 15 . 20 . 110 Citation issuance authority . A . Any officer of the Fire Prevention Bureau who has completed the mandatory course of peace officer training prescribed by Section 832 of the Cali €ornia Penal Code is hereby authorized , pursuant to Sections 832, 836 . 5 And 19 (d ) of the penal Code, and subject to the provisions thereo€ , to arrest a person without warrant whenever the officer has reasonable cause to believe that the peeson to be arrested has either violated in the officer ' s presence or failed to correct a violation of any provision of the Uniform Fire Code or the amendments thereto contained in this Code . S . Any officer of the Fire Prevention Bureau who has completed the course cif - t-raini,nq prescribed . by. Penal _Cade 8ecti6n 832 is further authorized, pursuant to Sect- ions 853 . 5 and 853 . 6 of the Penal Code, to issue a Notice to Appear to an arrested person and to release such person on his or her written promise to appear in Court . In the event that the arrested person demands to be taken before a magistrate or refuses to provide his or her written promise -52- to appear in court , the Fire Prevention Officer shall either summon a Redlands Police Officer and request that the violator be taken into custody, or contact the City Attorney and request that an infraction complaint against the violator be prepared and filed in the Municipal Court . C. In addition to the mandatory course of peace officer training prescribed by Section 832 of the California Penal Cade , the Chief of Police shall establish and cause to be administered a special enforcement training program designed to instruct the officers of the Fire Prevention Bureau with respect to the evidentiary prerequisites to Municipal Court prosecution, the procedures for issuing infraction citations, and otherwise prudently exercising their arrest and citation authority, and the limitations atterndant to such authority. D. The officers of the Fire Prevention Bureau who are authorized to issue citations pursuant to this section shall file copies of all executed citations with the Municipal Court, and also within the Fire Department . 15 . 20 . 120 Violation - penalty . A. It is unlawful to violate or to fail to comply with any of the provisions of the Uniform Fire Cade , or to fail to comply with any order made pursuant thereto, It is _S3- also unlawful to build in violation of any detailed statement of plans or speci £icatiorls submitted and approved under the Uniform Fire Code, or any certificate or permit 'slued thereunder , and from which no appeal has been taker . B. Except as otherwise specified in this section , all violations of the Uniform Fire Code or its appendices , or the araerndments thereto contained in this code are infrac- tions . All violations of Article 3 of the Uniform Fire code are misdemeanors . All violations of the Uniform Fire Code or its appendices , or the amendments thereto contained in this code are punishable as provided in Chapter 1 . 20 of this code . C. Every person who causes , aids , abets or conceals a violation of the Uniform Fire Code is guilty of violating the Uniform Fire Code . Each such person, firm or corpora- tion shall be deemed guilty of a separate offense for each day or portion thereof during which any violation of any provisions of the Uniform Fire Code is cow-fitted, continued, permitted or maintained by such person, firm or corpora- tILOn. " SECTION 2: If any section, subsection, sentence , clause or phrase of this Ordinance is for any reason held to be invalid, such holding or holdings shall not affect the -54- validity of the remaining portions of this ordinance . The City Council hereby declares that it mould have passed this ordinance and each section, subsection, sentence, clause and phrase thereof, irrespective of the Fact that any one or more sections , subsections, sentences, clauses or phrases be declared invalid . SECTION 3; The Mayor shall sign this ordinance and the City Clerk shall certify to the adaption of this ordinance and shall cause it ► or a gummary of it , to be published once in the Redlands Daily Facts , a newspaper of general circulation printed and published in the City. ay)6r , city, Fier , City/of Bedlam s -55- 1 , Lorri.e_-P-ovzer —0 City Clerk of the City OE Redlands , DO HEREBY CERTIFY that the foregoing is a true and correct copy of Ordinance NO , 2105 _ of said CitY whiCh was introauced at a regular meeting of the City CouncLl held on the 6th day of Fehr-uary . 1990 , and finally passed not less than five ( 5 ) days thereafter on the 20th day of February , 1990 , by the following vote, to-wit; ASSES : Councilmembers Beswick, Cunningham, Nilson; Mayor DeMirjyn NOES , None ABSTAIN: None ABSENT: Councilmember Larson �tvy erkl KAS0045